A/C SYSTEM MAINTENANCE - Continued
A/C SYSTEM MAINTENANCE - Continued

Field Maintenance Manual For M400T And M400W
Page Navigation
  641    642    643    644    645  646  647    648    649    650    651  
img
.
TM 5-3805-292-23
0093
EVACUATION CONTINUED
Figure 2. Evacuation Hook-Up.
0093
10. After 28 to 29 inHg (95 to 98 kPa) vacuum has been reached and held for an additional 90 minutes, close man-
ifold gauge set (Figure 2, Item 2) and valves (Figure 2, Items 3 and 7) completely.
11. Turn OFF vacuum pump. Refer to vacuum pump OEM manual for operation instructions.
N OT E
Excessive vacuum loss is an indicaton of a possible leak in the system.
i
Amount of vacuum loss in 5 minutes must no exceed 2 inHg (7 kPa). If vacuum loss
t
exceeds maximum, repair all leaks and repeat steps 1 through 11.
12. If vacuum loss does not exceed 2 inHg (7 kPa) in 5 minutes, system is ready to charge.
END OF TASK