TM 5-3805-298-23-1
0121
Table 1. Condenser Fan(s) Do Not Operate When the Heater A/C Switch Is in A/C Position - Continued.
0121
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
5. Visually inspect primary condenser
All Three A/C Condenser Fans Do
Condenser Fan(s) Do Not
Not Operate Proceed to Test Step 2.
fans (Figure 1, Item 1) and
Operate When the Heater A/
auxiliary fan (Figure 1, Item 2)
C Switch Is in A/C Position -
operation (TM 5-3805-298-10).
Continued
Does Not Operate Proceed to Test
Step 13.
Both Primary A/C Condenser Fans
Do Not Operate Proceed to Test
Step 22.
Primary A/C Condenser Fans 1
(Right Side) Only Does Not Operate
Proceed to Test Step 31.
Primary A/C Condenser Fans 2 (Left
Side) Only Does Not Operate
Proceed to Test Step 32.
Figure 1. Primary and Auxiliary Condenser Fans.