TM 5-3805-298-23-1
0121
Table 1. Condenser Fan(s) Do Not Operate When the Heater A/C Switch Is in A/C Position - Continued.
0121
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Test Step 10. Test for Shorted
Condenser Fan(s) Do Not
Auxiliary Condenser Fan Relay.
Operate When the Heater A/
C Switch Is in A/C Position -
Continued
(WP 0174), measure resistance
Proceed to step 2.
between connector MC-C1
Proceed to Test Step 11.
and terminal C.
Continuity Replace air conditioning
(WP 0174), test for continuity
condenser fans wiring harness
between connector MC-C1
(WP 0418).
Proceed to Test Step 33.
and ground.
No Continuity Replace A/C
Proceed to Test Step 33.
Test Step 11. Test for Shorted
Auxiliary Air Conditioning
Condenser Fan Wiring Harness.
1. Disconnect connector MC-C2
auxiliary condenser fan relay.
Continuity Replace auxiliary air
(WP 0174), test for continuity
conditioning condenser fan wiring
between connector MC-C1
harness (WP 0419).
Proceed to Test Step 33.
and terminal C.
No Continuity Replace auxiliary
Figure 137).
Proceed to Test Step 33.
Test Step 12. Test for Shorted Air
Conditioning Condenser Fans
Wiring Harness.
1. Disconnect connector MA-C4
condenser fans relay.
Continuity Replace air conditioning
(WP 0174), test for continuity
condenser fans wiring harness
between connector MA-C2
(WP 0418).
Proceed to Test Step 33.
and terminal C.
Proceed to Test Step 33.
0121-8