TM 5-3805-291-23-1
TROUBLESHOOTING WITHOUT A DIAGNOSTIC CODE - CONTINUED
0008 00
Table 8. AC System Troubleshooting - Continued.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
12. The system has air or moisture and does 1. Recover refrigerant (WP 0225 00) and
1. Temperature of Air Flow is
repair leaks.
not have a full charge of refrigerant.
Partially Cool - Continued.
Perform Refrigerant Leakage Test (WP 2. If a large amount of refrigerant was
lost, perform Refrigerant Compressor
3. Evacuate system and re-charge system
with correct amount of refrigerant (WP
0225 00).
4. After system is charged, operate for a
minimum of 10 minutes (TM 5-3805-
291-10) and perform Performance
verify correct operation of AC system.
N OT E
Compressor has internal leaks.
Read valve has leakage.
13. Check drive belt for damage or
If belt is loose or damaged, replace belt
looseness.
00) as necessary.
14. Perform Refrigerant Leakage Test (WP 1. If an internal leak is found, replace
line dryer (WP 0224 00).
2. If an external leak such as a hose
connection is found, recover
refrigerant (WP 0225 00) and repair
leaks.
3. Evacuate and charge system with
correct amount of refrigerant. Measure
refrigerant by weight (WP 0225 00).
4. If a large amount of refrigerant was
lost, perform Refrigerant Compressor
5. After system is charged, operate for a
minimum of 10 minutes (TM 5-3805-
291-10) and perform Performance
verify correct operation of AC system.
0008 00-96