TM 5-3805-291-23-1
TROUBLESHOOTING WITHOUT A DIAGNOSTIC CODE - CONTINUED
0008 00
Table 8. AC System Troubleshooting - Continued.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4. Check for restrictions, insects, foreign
8.
remove all blockages.
Engaged but System Has
restriction of air flow through
2. If problem still exists, go to Test 5.
Insufficient Cooling -
condenser.
Continued.
5. Check inlet and outlet on accumulator
1. If inlet and outlet are warm, charge
for warmth.
system with correct amount of
refrigerant. Measure refrigerant by
weight (WP 0225 00).
2. If problem still exists, go to Test 6.
6. Perform Refrigerant Leakage Test (WP 1. Recover refrigerant (WP 0225 00) and
repair leaks.
2. If a large amount of refrigerant was
3. Evacuate system and re-charge system
with correct amount of refrigerant (WP
0225 00).
4. After system is charged, operate for a
minimum of 10 minutes (TM 5-3805-
291-10) and perform Performance
verify correct operation of AC system.
0008 00-102