Table 1. Air Conditioner Does Not Blow Cold When A/C Is Turned On and
Temperature Control Panel Is Set on Maximum Cool - Continued.
0118
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Air Conditioner Does Not
9. Inspect auxiliary condenser fan
Auxiliary Condenser Fan Guard OK -
Blow Cold When A/C Is
guard (Figure 6, Item 1) for dirt,
Proceed to step 10.
Turned On and Temperature
debris, or damage.
Auxiliary Condenser Fan Guard Has
Control Panel Is Set on
Dirt or Debris - Remove dirt and debris,
Maximum Cool Continued
proceed to Test Step 8.
Auxiliary Condenser Fan Guard
Damaged - Replace auxiliary
condenser (WP 0419).
Proceed to Test Step 8.
Auxiliary Condenser Fan OK - Install
(Figure 6, Item 2) for bent or
damaged fan blades.
Proceed to step 11.
Auxiliary Condenser Fan Damaged -
Replace auxiliary condenser
(WP 0419).
Proceed to Test Step 8.
Figure 6. Auxiliary Condenser Fan.