TM 5-3805-298-23-1
0118
Table 1. Air Conditioner Does Not Blow Cold When A/C Is Turned On and
Temperature Control Panel Is Set on Maximum Cool - Continued.
0118
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Air Conditioner Does Not
Test Step 3. Low Pressure Gauge
Blow Cold When A/C Is
and High Pressure Gauge Are Above
Turned On and Temperature
Normal.
Control Panel Is Set on
1. Inspect primary condenser
Maximum Cool Continued
(Figure 1, Item 1) for dirt, debris,
step 2.
bent fins (Figure 1, Item 2), or
Primary Condenser Has Dirt or
damage.
Debris - Remove dirt and debris.
Proceed to Test Step 8.
Primary Condenser Damaged or Has
Bent Fins - Straighten primary
condenser (WP 0417).
Proceed to Test Step 8.
Figure 1. Primary Condenser.
0118