TM 5-3805-298-23-1
0118
Table 1. Air Conditioner Does Not Blow Cold When A/C Is Turned On and
Temperature Control Panel Is Set on Maximum Cool - Continued.
0118
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Air Conditioner Does Not
4. Inspect each primary condenser
Blow Cold When A/C Is
fan guard (Figure 3, Item 1) for dirt,
Proceed to step 5.
Turned On and Temperature
debris, or damage.
Control Panel Is Set on
Dirt or Debris - Remove dirt or debris.
Maximum Cool Continued
Proceed to Test Step 8.
fan (WP 0417).
Proceed to Test Step 8.
5. Inspect each primary condenser
fan blade (Figure 3, Item 2) for
primary condenser fan cover
damage or bent blades.
(WP 0417).
Proceed to step 6.
Primary Condenser Fan Damaged or
Has Bent Blades - Replace primary
condenser fan (WP 0417).
Proceed to Test Step 8.
Figure 3. Primary Condenser Fan.
0118